Main Input Voltage
230 V
400 V 3 phases
Other Input Voltage
220 V
240 V
Main Output Voltage
230 V
Other Output Voltage
220 V
240 V
rated power in W
12000 W
rated power in VA
15000 VA
nb of power socket outlets
2 IEC Jumpers
8 IEC 60320 C19
output connector type
Hard wire 3-wire (H N + E) 1
Hard wire 5-wire (3P + N + E) 1
number of rack unit
12U
battery type
Lead-acid battery
Physical
colour
Black
height
53.3 cm
width
43.2 cm
depth
77.3 cm
net weight
247.73 kg
mounting location
Front
mounting preference
Lower
mounting mode
Rack-mounted
two post mountable
0
USB compatible
No
Input
network frequency
40…70 Hz auto-sensing
number of input connectors
1 hard wire 3-wire (1P + N + E)
1 hard wire 5-wire (3P + N + E)
input voltage limits
160…280 V
maximum input current
90 A
switching current capacity
100 A
input harmonic distortion
Less than 5 % for full load
input current
90 A (1 phase)
30 A per phase (3 phases)
load power factor
0.8
Input Power Factor at Full Load
0.95
Output
Maximum configurable power in W
12000 W
harmonic distortion
Less than 5 %
output frequency
50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
crest factor
3 : 1
UPS type
Double conversion online
Wave type
Sine wave
output overload operation
60 seconds at 125% and 30 seconds at 150%
bypass type
Built-in static bypass
Internal bypass (automatic and manual)
Optional external bypass
efficiency
93 % (in battery operation)
Maximum configurable power in VA
15000 VA